Project index

Case study 01

Commercial LV Cabling Design

Evidence verified - sanitised write-up

Standards-traceable 400 V cabling design for a three-tenancy commercial complex: maximum demand, cable selection, earthing, and fault verification to AS/NZS 3000 and AS/NZS 3008.1.1.

One-line diagram of a 400 V three-tenancy installation from supply transformer to distribution boards
Scope
Power design, standards, verification
Role
Sole designer (coursework)
Status
Evidence verified - sanitised write-up

Problem

What needed solving

Design the complete LV cabling system for a three-tenancy commercial complex supplied at 400 V from a 500 kVA transformer, and prove every cable and protective device against AS/NZS 3000:2018 and AS/NZS 3008.1.1:2025.

Approach

How the work is framed

Calculated per-phase maximum demand by the AS/NZS 3000 Clause 2.2.2(a) method, then ran one auditable nine-step selection chain per cable covering current capacity, de-rating, voltage drop, fault level, and earth-fault-loop impedance, with every assumption logged for verification against the controlling standard.

Result

Current public outcome

123.6 A design current met by 25 mm² X-90 copper consumer mains at 0.74 % voltage drop; 8.0 kA prospective fault current at the main switchboard confirmed 10 kA-rated Type C protection; every final subcircuit passed the AS/NZS 3000 Table 8.1 earth-fault-loop limits.

Evidence status

What still needs proof

Verified. Sanitised public write-up complete; full tabulated working held privately because standards tables are Standards Australia copyright.

Design detail

The full selection chain

Every cable in this design was selected with the same auditable nine-step chain: design current, protective device, installation method, correction factors, cable selection, voltage drop, fault withstand, earth-fault-loop check, final selection. The worked results below are my calculations; standards table data is cited by table number, not reproduced, because those tables are Standards Australia copyright.

Design basis

Three-tenancy commercial complex (a small supermarket, a hairdresser and a butcher, plus communal services), supplied at 400 V three-phase (230 V line-to-neutral) from a 500 kVA transformer with a stated prospective fault current of 15 kA at the transformer. Cable selection to AS/NZS 3008.1.1:2025; installation, earthing, protection and maximum demand to AS/NZS 3000:2018 (+ Amdt 1–3, Ruling 1:2024).

Maximum demand and phase balance

Maximum demand was determined by calculation per AS/NZS 3000:2018 Clause 2.2.2(a), using the Table C2 non-domestic diversity method. Every load was classified once, allocated to a phase, and group-diversity rules applied per phase; three-phase loads add their per-phase current to all three phases. The heaviest phase sets the design current: 123.6 A on phase A, with 7.5 % phase imbalance. Per board: communal 39.9 A, supermarket 39.1 A, hairdresser 24.5 A, butcher 41.8 A. The butcher is simultaneously the heaviest-loaded and longest (15 m) submain.

Consumer mains: worked chain

X-90 single-core copper, separate conduits laid in trefoil, buried 600 mm, soil 20 °C, 15 m route. AS/NZS 3008.1.1:2025 Table 3.8 routes this arrangement to Table 3.13, Column 19 (separately enclosed).

Step 1  Design current    Ib = 123.6 A (heaviest phase)
Step 2  Protective device In = 125 A Type C   (Ib <= In)
Step 3  Install method    Table 3.8 -> Table 3.13, Col 19
Step 4  Correction        k = 1.04 (soil, T3.45) x 0.99 (depth, T3.46)
                            = 1.03
        Required tabulated CCC >= 125 / 1.03 = 121.4 A
Step 5  16 mm2 -> 101 A (fail);  25 mm2 -> 132 A (pass)
        Iz = 132 x 1.03 = 136 A -> Ib 123.6 <= In 125 <= Iz 136  OK
Step 6  Voltage drop (limit 1 % = 4.0 V), Rc = 0.927 ohm/km
        dV = sqrt3 x 123.6 x 15 x 0.927 / 1000 = 2.98 V = 0.74 %  OK
Step 7  PFC at MSB = 8.0 kA; breaking capacity 10 kA  OK
SELECT  25 mm2 X-90 Cu active and neutral; 6 mm2 Cu earth

A single-conduit arrangement (Column 17) would instead require 35 mm²; that is not the arrangement specified. The result is current-carrying-capacity driven, not voltage-drop driven.

Submains: worst case worked

V-75 single-insulated copper, one conduit, buried 1 m, soil 20 °C. Table 3.8 routes this to Table 3.12, Column 17. Combined correction k = 1.05 × 0.95 = 1.00. The butcher submain governs.

Step 1  Ib = 41.8 A          Step 2  In = 50 A Type C
Step 4  k = 1.00 -> required CCC >= 50 A
Step 5  6 mm2 -> 45 A (fail); 10 mm2 -> 59 A (pass); Iz = 59 A
        Ib 41.8 <= In 50 <= Iz 59  OK
Step 6  dV = sqrt3 x 41.8 x 15 x 2.23 / 1000 = 2.42 V = 0.61 %  OK
SELECT  10 mm2 V-75 Cu; 4 mm2 Cu earth
        (16 mm2 recommended for practical margin)

Final subcircuits: the thermal-insulation catch

The specification states thermal insulation in all ceiling spaces, and the final subcircuits clip across the ceiling joists, so the cables are not in free air. A cable clipped to a structural member within bulk insulation is a partially-surrounded thermal-insulation installation under AS/NZS 3008.1.1 Clause 3.4.3. Ratings were therefore read from the partially-surrounded column with the 45 °C ambient correction (Table 3.44, factor 0.93). This condition raised most power circuits from 2.5 mm² to 4 mm², the single most consequential installation-condition decision in the design.

Load typeRun (m)Ib (A)In (A)CableIz (A)ΔVEarth
Lighting265.0101.5 mm²11.21.87 %1.5 mm²
Power (10 A GPO)2410204 mm²21.41.17 %2.5 mm²
Power >10 A (15 A socket)1515204 mm²21.41.10 %2.5 mm²
Hot water service1815.7204 mm²21.41.37 %2.5 mm²
Cooking appliances1511.3164 mm²21.40.83 %2.5 mm²
Air-conditioning (3-ph)104.6/ph102.5 mm²15.80.18 %2.5 mm²
3-phase 15 A outlet1015/ph204 mm²21.40.36 %2.5 mm²

All Iz ≥ In and every voltage drop is within budget; the worst-case total path (mains + butcher submain + lighting final) sums to 3.2 % against the 5 % limit.

Earthing and protection

Protective earthing conductors were sized from AS/NZS 3000:2018 Table 5.1 on the MEN system, main earth connected at the MSB neutral bar. Because the 25 mm² consumer-mains active was set by current-carrying capacity and not upsized for voltage drop, the 6 mm² main earth follows directly from Table 5.1. Type C circuit breakers were used throughout (suited to the low inrush of LED lighting, resistive heating and small motors), with 30 mA RCDs on all final subcircuits up to 32 A supplying socket-outlets and lighting. Nominal-current grading (125 A, then 40 to 50 A, then 10 to 20 A) gives current discrimination; full selectivity is to be confirmed against manufacturer time–current curves, a stated limitation of scope.

Fault level and earth-fault loop

Source impedance  Zs = 400 / (sqrt3 x 15 000) = 0.0154 ohm/phase
Consumer mains    R  = 0.884 x 15 / 1000     = 0.0133 ohm
Z at MSB   = 0.0154 + 0.0133 = 0.0287 ohm
PFC at MSB = 230 / 0.0287    = 8 014 A = 8.0 kA

All device breaking capacities (10 kA) exceed the local prospective fault current. Earth-fault-loop impedance was checked for the longest circuit of each conductor size against AS/NZS 3000:2018 Table 8.1 for Type C breakers; the worst-case loop (4 mm² general-power final, 24 m, on the butcher submain) gives Zs ≈ 0.57 Ω against a limit of ≈ 1.15 Ω. The external loop impedance Ze = 0.0345 Ω is a declared assumption; the real figure comes from the network operator's connection-point fault data or an on-site loop-impedance measurement.

Declared assumptions and limits

Assumptions are logged explicitly rather than hidden: the socket-outlet diversity basis, the consumer-mains conduit arrangement (Column 19 basis confirmed against the controlled 2025 edition at transcription), the assumed Ze above, and discrimination pending manufacturer curves. The partially-surrounded ratings used were cross-checked against the 2017 edition and confirmed unchanged in the 2025 edition. Final values are to be verified against the controlling standards and network authority at installation. This write-up is sanitised from graded coursework: the design scenario is paraphrased, and no standards table content is reproduced.